GF Solar Tracker Controller Passes Low-Temperature Test

DC Tracker Control Unit Low-Temperature

Performance Test

Verifying TCU device stability at -40°C extreme conditions

Test Overview

 

Test Purpose

Verify whether the TCU device functions normally after low-temperature treatment

 

Testing Standards

GB/T 29320-2024 Chapter 16, Section 16.1 "Low-Temperature Test"

 

Test Sample

Tracking Control Unit (TCU) GF-S-TCU-V1.0 (1 set)

 

Test Date

July 9, 2025

 

Test Location

No. 2 Courtyard, Southeast Corner of Dehui Street and Wenjin North Road, Zheng'an Town, Zhongmu County, Zhengzhou, Henan

 

Environmental Conditions

Temperature: 35.3℃ | Humidity: 52% RH | Weather: Sunny

Test Methods and Procedures

 

Test Equipment

High-Low Temperature Test Chamber

 

Test Procedure Steps

  1. Place the non-powered TCU into the High-Low Temperature Test Chamber, set to -40℃
  2. Store at -40℃ for 16 hours
  3. Gradually warm the chamber to -25℃ at a rate not exceeding 1℃/min, then maintain for 2 hours
  4. Power on and operate for 2 hours, recording system status
  5. Operate at room temperature for 2 hours
  6. Test in both automatic and manual modes, recording system status

Test Results and Conclusions

Test Requirements TCU must be shut down and stored at -40℃ for 16 hours, then warmed up to -25℃, and removed after 2 hours for room temperature testing
Test Content Various operating mode tests and parameter settings Tracking function Control function Protection and storage function Communication and synchronization function Tracking range and accuracy Drive unit
Test Results OK OK OK OK OK OK OK
Conclusion The TCU can function normally after low-temperature treatment
 

Performance Verified

All functions operating within specifications after extreme cold exposure

 

Temperature Resilience

TCU withstands -40℃ for 16 hours without performance degradation

 

Stable Operation

No issues during power-up and operation after temperature cycling

Test Photos

TCU at -40℃
TCU shut down at -40℃ and stored for 16 hours
Test Chamber
35.30℃
Monitoring
-40℃
TCU at -25℃
TCU warms up to -25℃, shuts down, and stores for 2 hours
Post-Test
-25℃
Operation Test
-24.99℃

Request the Complete Test Report

Contact the GF Solar team for the detailed test report and technical specifications